Hardware Specification
The WP500 Gateway is engineered with a robust hardware architecture to address the demands of industrial applications. Below are the detailed hardware specifications of the WP500, outlining its key components and features:
WP500 Specifications
System Specification |
|
Processor |
ARM Quad-core 1.6Ghz per core. |
Flash Memory |
8GB Flash Memory |
RetentiveData Storage |
NVRAM 32 MB |
Number of Supported Devices |
Max 256 I/O Modules Supported. |
Diagnostic Display |
Internal through Web Interface |
Redundancy |
Yes |
Protocols Supported |
MODBUS, DNP 3.0, PROFINET, MQTT, OPC UA, SFTP, SMTP, OpenVPN, EtherNet/IP |
Programming Language Supported |
IEC-61131-3 Languages (IL, ST, LD, FBD & SFC),C/C++, Java, Python |
Power Input |
|
Input Voltage |
24 VDC |
Input Current |
Max 504 mA (With 1A at Ubus for the I/O & UL = 24 V) |
Protective Circuit |
Surge Protection; Electronic |
|
Reverse Polarity Protection; Electronic |
Connectors |
|
Ethernet Ports |
3 Ports, RJ45 |
Input Voltage |
Independent Networks with Unique MAC & IP Address |
Input Current |
Auto Negotiation and Auto Crossing |
Protective Circuit |
Network Speed 10/100/1000 Mbps |
|
Protocols TCP/IP, ARP, UDP, Modbus UDP/TCP, Modbus ASCII/RTU |
Serial Ports |
|
|
RS 485 (Port 1): Screw Terminals (A1, B1, G1) |
|
RS 485 (Port 2): Screw Terminals (A2, B2, G2) |
USB Port |
USB Type C |
Insulation Characteristics |
|
Protection Class |
EN/IEC 61010-1, CE |
System Requirements |
|
Engineering Tool |
WP Work Bench |
Application Interface |
Web Interface |
Environmental Specification |
|
Degree of Protection |
IP30 |
Ambient Temperature |
|
(Operation) |
-40 to 70 |
Ambient Temperature |
-40 to 85 |
Permissible Humidity (Operation) |
10% to 95% (non-condensing) |
Permissible Humidity |
10% to 95% (non-condensing) |
Shock (Operation) |
IEC 60068-2-27; Half Sine, 15 G, 11 msec Duration |
Vibration (Operation) |
IEC 60068-2-6; 5-100 Hz 0.7 G |
Environmental and Usage Limit |
|
Pollution Degree |
Rated for Pollution Degree 2 environment, suitable for locations with non-conductive pollution |
Altitude Range |
Up to 200 meters above sea level. |
Over Voltage Category |
The device is classified under Category III, suitable for industrial power distribution. |
Mechanical |
|
Dimension |
Width 40mm |
|
Height 130 mm |
|
Depth 85 mm |
Weight |
360 g |
Table: 001
Created with the Personal Edition of HelpNDoc: Maximize Your Productivity with a Help Authoring Tool