DNP3M_READGROUP
Issue a read request for a specific object group / variation for the specified session.
Inputs
Parameter |
Data type |
Description |
EN |
BOOL |
Trigger : activate if TRUE |
SESN |
UINT |
Session number defined in configurator |
GRP |
UINT |
Object group for read request |
VART |
UINT |
Object variation to read. Valid range depends on the object group and the capabilities of the Outstation. |
QUAL |
UINT |
RANGE_NONE, RANGE_STARTSTOP, RANGE_COUNT See // Qualifier in the section “Command and status values (K5BusDNP3MCD)”. |
START |
UINT |
Start point index if RANGE_STARTSTOP |
STOP |
UINT |
Stop point index if RANGE_STARTSTOP or quantity if RANGE_COUNT |
Outputs
Parameter |
Data type |
Description |
READY |
BOOL |
TRUE if the block is ready for a new command |
RC |
DINT |
See // RC_CMD in the section “Command and status values (K5BusDNP3MCD)”. -1 if activation fails. |