DNP3M_FREEZCNEX
Issue a counter freeze request (NOACK can be set).
Inputs
Parameter |
Data type |
Description |
EN |
BOOL |
Trigger : activate if TRUE |
SESN |
UINT |
Session number defined in configurator |
CLEAR |
BOOL |
If TRUE, Freeze and clear function code is used. |
QUAL |
UINT |
RANGE_NONE, RANGE_STARTSTOP See // Qualifier in the section “Command and status values (K5BusDNP3MCD)”. |
NOACK |
BOOL |
If TRUE, NOACK function code is used. |
START |
UINT |
Start point index if RANGE_STARTSTOP |
STOP |
UINT |
Stop point index if RANGE_STARTSTOP |
Outputs
Parameter |
Data type |
Description |
READY |
BOOL |
TRUE if the block is ready for a new command |
RC |
DINT |
See // RC_CMD in the section “Command and status values (K5BusDNP3MCD)”. -1 if activation fails. |
DNP3M_FREEZCNEX |
IEC 61131-3 Automation platform > Programming - Reference guide > Driver specific function blocks > DNP3 Master > K5BusDNP3MCD function block description and status codes > DNP3M_FREEZCNEX |