Issue a binary output command. (CROB, object group 12)

Inputs

Parameter

Data type

Description

EN

BOOL

Trigger : activate if TRUE

SESN

UINT

Session number defined in configurator

PNUM

UINT

Point number

FC

UINT

COMMAND_SBO, COMMAND_DIRECTOPERATE, COMMAND_DIRECTOPERATE_NOACK

See // Function_Code in the section “Command and status values (K5BusDNP3MCD)”.

CONTROL

UINT

CR << 15 | OpType << 8 | TCC

Control Code, Operation Type, TCC.

See // Values for control code of CROB in the section “Command and status values (K5BusDNP3MCD)”.

QUAL

UINT

RANGE_COUNT

See // Qualifier in the section “Command and status values (K5BusDNP3MCD)”.

TON

TIME

Ontime ms

TOFF

TIME

Offtime ms

Outputs

Parameter

Data type

Description

READY

BOOL

TRUE if the block is ready for a new command

RC

DINT

See // RC_CMD in the section “Command and status values (K5BusDNP3MCD)”. -1 if activation fails.


Created with the Personal Edition of HelpNDoc: Easily Add Encryption and Password Protection to Your PDFs