DNP3M_CMDBIN
Issue a binary output command. (CROB, object group 12)
Inputs
|
Parameter |
Data type |
Description |
|
EN |
BOOL |
Trigger : activate if TRUE |
|
SESN |
UINT |
Session number defined in configurator |
|
PNUM |
UINT |
Point number |
|
FC |
UINT |
COMMAND_SBO, COMMAND_DIRECTOPERATE, COMMAND_DIRECTOPERATE_NOACK See // Function_Code in the section “Command and status values (K5BusDNP3MCD)”. |
|
CONTROL |
UINT |
CR << 15 | OpType << 8 | TCC Control Code, Operation Type, TCC. See // Values for control code of CROB in the section “Command and status values (K5BusDNP3MCD)”. |
|
QUAL |
UINT |
RANGE_COUNT See // Qualifier in the section “Command and status values (K5BusDNP3MCD)”. |
|
TON |
TIME |
Ontime ms |
|
TOFF |
TIME |
Offtime ms |
Outputs
|
Parameter |
Data type |
Description |
|
READY |
BOOL |
TRUE if the block is ready for a new command |
|
RC |
DINT |
See // RC_CMD in the section “Command and status values (K5BusDNP3MCD)”. -1 if activation fails. |
DNP3M_CMDBIN |
|
IEC 61131-3 Automation platform > Programming - Reference guide > Driver specific function blocks > DNP3 Master > K5BusDNP3MCD function block description and status codes > DNP3M_CMDBIN |