DNP3M_CMDANLG
Issue an Analog Output Command (AOB, object group 41).
Inputs
Parameter |
Data type |
Description |
EN |
BOOL |
Trigger : activate if TRUE |
SESN |
UINT |
Session number defined in configurator |
PNUM |
UINT |
Point number |
FC |
UINT |
COMMAND_SBO, COMMAND_DIRECTOPERATE, COMMAND_DIRECTOPERATE_NOACK See // Function_Code in the section “Command and status values (K5BusDNP3MCD)”. |
VART |
UINT |
Object variation to use in request |
QUAL |
UINT |
Qualifier - RANGE_COUNT See // Qualifier in the section “Command and status values (K5BusDNP3MCD)”. |
VALUE |
ANY |
Value to write - can be any data type |
Outputs
Parameter |
Data type |
Description |
READY |
BOOL |
TRUE if the block is ready for a new command |
RC |
DINT |
See // RC_CMD in the section “Command and status values (K5BusDNP3MCD)”. -1 if activation fails. |
DNP3M_CMDANLG |
IEC 61131-3 Automation platform > Programming - Reference guide > Driver specific function blocks > DNP3 Master > K5BusDNP3MCD function block description and status codes > DNP3M_CMDANLG |
Created with the Personal Edition of HelpNDoc: Full-featured multi-format Help generator